Short answer

In a two-wire loop, the same current travels through the supply, transmitter, cable, and input load. The transmitter uses part of the available voltage to operate while controlling the current that represents the measured value.

4–20 mA current loop diagramA 24 volt supply powers a transmitter and returns a 4–20 mA signal to a PLC analog input.TWO-WIRE CURRENT LOOP24 V DCSUPPLYTRANSMITTER4–20 mAPLC AIINPUT+ loopsignalreturn / commonREAD HERE Original diagram · Signal Field Guide / field note signal basics

Quick reference: 24 V DC Current Loop Power Budget & Voltage Drop Breakdown

24 V DC Current Loop Power Budget & Voltage Drop Breakdown
Series Component in 4–20 mA LoopNominal Resistance (Ω)Voltage Drop at 4 mA (0%)Voltage Drop at 20 mA (100%)Operating Impact
Two-Wire Transmitter (Internal Electronics)Dynamic (equivalent)10.50 V – 12.00 V (Fixed Min)10.50 V – 12.00 V (Fixed Min)Minimum compliance voltage required for internal circuitry
PLC Analog Input Sampling Shunt250 Ω ±0.1%1.00 V DC5.00 V DCTranslates loop current into 1.0 V to 5.0 V ADC input voltage
Intrinsic Safety Zener Barrier250 Ω – 350 Ω1.00 V – 1.40 V DC5.00 V – 7.00 V DCEssential in hazardous Ex areas; consumes major voltage budget
Local Digital Loop Indicator50 Ω – 100 Ω0.20 V – 0.40 V DC1.00 V – 2.00 V DCOptional field readout; adds series burden
500 ft (150 m) 18 AWG Twisted Pair~6.5 Ω (loop path)0.03 V DC0.13 V DCMinor voltage loss in typical plant runs
2,500 ft (750 m) 18 AWG Twisted Pair~32.5 Ω (loop path)0.13 V DC0.65 V DCSignificant voltage drop; must be factored into total budget

What to look for

The loop must leave enough voltage at the transmitter at the highest required current. Cable resistance, barriers, isolators, and input resistance all consume part of the budget.

A loop that works at room temperature but fails at the top of the range may be running out of voltage headroom. Measure the voltage at the transmitter, not only at the power supply.

FIELD CASE / REASONING PATH

When the symptom appears in the plant

A pressure transmitter loop included the field device, a local digital indicator, and the PLC input card. The PLC constantly reported a 'Wire Break' error, but the transmitter seemed to function when connected directly to a calibrator. The technician calculated the total loop resistance and found it exceeded the 600-ohm limit of the 24V power supply. The local indicator added too much burden. Upgrading to a higher compliance voltage supply solved the problem.

Safety & Meter Pitfall

The Transmitter Bench Supply Calibration Deception

A transmitter calibrated on an instrumentation workshop bench powered by an isolated 24.0 V DC bench power supply with zero external series resistance will behave flawlessly. When that same device is installed in the field—where 250 Ω of PLC resistance, a 300 Ω intrinsic safety barrier, and 1,000 feet of field cable introduce over 580 Ω of total loop burden—the loop voltage drops by 11.6 V at 20 mA. If the cabinet supply sags to 22.0 V, the transmitter receives only 10.4 V, starving its sensing amplifier. The technician will observe the transmitter working normally from 4 mA to 15 mA, and then mysteriously freezing or clipping at exactly 15.2 mA. Always test and verify transmitter calibration with the full operational field loop resistance in circuit.

DIAGNOSTIC SEQUENCE

Five checks before replacement

  1. Calculate the total loop resistance by summing the resistance of the wiring, the PLC input card (typically 250 ohms), and any other loop devices.
  2. Determine the maximum allowable loop resistance based on the power supply voltage (e.g., for a 24V supply and 12V transmitter minimum, (24-12)/0.02 = 600 ohms max).
  3. Measure the voltage across the transmitter terminals while forcing a 20mA signal; it must remain above the manufacturer's specified minimum operating voltage.
  4. Verify the power supply capacity; it must provide enough current for all loops on the circuit simultaneously (assume 20mA per loop).
  5. Check for 'hidden' resistance sources, such as corroded terminals, intrinsic safety barriers, or very long cable runs of thin gauge wire.
PRACTICAL NOTES

Always check the burden voltage of passive loop displays or chart recorders; they often drop 3-5 volts from the loop.

A 250-ohm precision resistor is commonly used at the PLC to convert a 4-20mA current loop into a 1-5V voltage signal.

When using intrinsically safe barriers, remember they add significant resistance to the loop.

BEFORE YOU REPLACE THE PART

Bench checklist

  • Calculate total loop resistance: R_loop = R_receiver + R_barrier + R_cable_roundtrip.
  • Verify transmitter minimum operating voltage (typically 10.5 V to 12.0 V DC) under maximum 20.0 mA loop current.
  • Measure power supply voltage under full load to ensure it does not sag below 23.5 V DC.
  • Check that no secondary devices in the loop are sharing an unisolated common ground.
  • Confirm whether the transmitter is a 2-wire loop-powered (passive) or 4-wire externally-powered (active) device.

Reference families

  • ISA-50.1 Standard
  • Instrument Loop Design Guidelines

Always verify the current edition and the exact device manual for the installation.

READ THE PRIMARY MATERIAL

Official references

These links point to standards bodies, industry organizations, or manufacturer documentation. Standards landing pages may require purchase or institutional access.

MV
FIELD INSTRUMENTATION & CONTROLS SPECIALIST

Marcus Vance, PE

16+ Yrs Field Exp

Marcus is a licensed Professional Engineer specializing in industrial process automation, PLC/DCS I/O commissioning, and instrumentation troubleshooting across petrochemical and manufacturing facilities.

Peer-reviewed for IEC & ISA standards compliance · Editorial methodology →
This note is an educational reference, not a substitute for the equipment manual, site procedures, or qualified electrical work.