BENCH TOOLS / 01
Numbers you can
use at the cabinet.
Small calculators for translating a reading into the next sensible question. No account. No spreadsheet ceremony.
FIELD
READY
READY
01
4–20 mA converter
Translate a measured current into engineering units.
FORMULA
low + ((mA − mAmin) ÷ (mAmax − mAmin)) × (high − low)ENGINEERING VALUE50.000 to 100 range
4 mA20 mA
Inside the configured range. The signal is giving you a usable reading.
02
Loop load check
Estimate the voltage consumed by a known loop resistance.
At 12.00 mA, this resistance uses3.00 Vleaving approximately 21.00 V for the transmitter and input.
03
Signal quality, by symptom
A quick handoff from number to next check.
01Stable but wrong →
Check scaling, range selection, and whether the input expects current or voltage.
02Wandering value →Check routing near drives, shield termination, reference points, and loose terminals.
03Zero or saturated →Check supply, polarity, continuity, and the input card’s live-zero configuration.
LOOKING FOR CONTEXT?Browse the symptom index →