Small calculators for translating a reading into the next sensible question. No account. No spreadsheet ceremony.
FIELD
READY
READY
01
4–20 mA converter
Translate a measured current into engineering units.
FORMULA
low + ((mA − mAmin) ÷ (mAmax − mAmin)) × (high − low)ENGINEERING VALUE50.000 to 100 range
4 mA20 mA
Inside the configured range. The signal is giving you a usable reading.
02
Loop load check
Estimate the voltage consumed by a known loop resistance.
At 12.00 mA, this resistance uses3.00 Vleaving approximately 21.00 V for the transmitter and input.
03
Signal quality, by symptom
A quick handoff from number to next check.
01Stable but wrong
Check scaling, range selection, and whether the input expects current or voltage.
02Wandering value
Check routing near drives, shield termination, reference points, and loose terminals.
03Zero or saturated
Check supply, polarity, continuity, and the input card’s live-zero configuration.