Short answer

An inductor resists changes in current according to Faraday's law of induction: V = −L * (di/dt). When a PLC digital output transistor abruptly shuts off power to a standard 24 V DC solenoid valve drawing 1.0 A, current drops to zero within microseconds. The collapsing magnetic field forces a severe reverse-polarity voltage transient—frequently exceeding −300 V to −500 V—across the switching contacts.

PNP sensor to PLC input wiring diagramA three-wire PNP sensor sends positive voltage to a PLC input.PNP / SOURCING OUTPUTSENSOR3-wire DCPLC INPUTsinking / common −I0.0+24 V / brownsignal / black0 V / blue Original diagram · Signal Field Guide / field note power & wiring

Quick reference: Inductive Surge Suppression Methods for 24 V DC Solenoids & Relays

Inductive Surge Suppression Methods for 24 V DC Solenoids & Relays
Suppression MethodClamping Voltage PeakMechanical Drop-Out DelayComponent ComplexityRecommended Application
Reverse Flyback Diode (1N4007)+0.7 V above supply rail (~25 V DC)Significant delay (+15 ms to +35 ms)Lowest (single diode across coil)General industrial valves, non-time-critical solenoids
Zener Diode + Fast Diode (TVS)Zener breakdown voltage (~36 V to 48 V)Minimal delay (+2 ms to +5 ms)Moderate (two diodes back-to-back)High-speed sorting gates, injection valves, fast packaging
Metal Oxide Varistor (MOV)Clamps at ~39 V to 56 V DCLow delay (+3 ms to +8 ms)Low (bidirectional bidirectional disk)Standard relay coils, AC/DC dual-voltage installations
RC Snubber (Resistor-Capacitor)Gradual slope, suppresses dV/dtLow to moderate delay (+5 ms to +12 ms)Moderate (tuned R and C components)Electromechanical relay contacts switching inductive loads
Unsuppressed (Open Coil)Negative spike exceeds −300 V to −600 VZero artificial delay (fastest mechanical open)None (no parts)Prohibited in modern PLC panels: causes immediate transistor failure

What to look for

Without suppression, this high-voltage transient punches through the PN junction of solid-state PLC output transistors (MOSFETs or bipolar transistors), resets nearby 24 V DC microcontrollers through electromagnetic radiation, or causes severe contact pitting and welding in electromechanical relays. A simple 1N4007 silicon diode connected in reverse-bias across the solenoid terminals clamps the transient to approximately +0.7 V above the supply rail.

There is an operational trade-off: a standard flyback diode recirculates coil current during decay, causing a noticeable mechanical dropout delay (15 to 40 ms) that can slow down high-speed sorting gates or pneumatic cylinders. In high-cycle applications where fast release is mandatory, a Zener-diode combination (transient voltage suppressor) or an RC snubber is preferred because it dissipates the magnetic energy faster while clamping voltage to a safe 36 V to 48 V threshold.

FIELD CASE / REASONING PATH

When the symptom appears in the plant

A custom automated assembly machine suffered recurring failures of transistor output cards on an Allen-Bradley Point I/O rack. Every three to four weeks, output point 2 or 4 would weld internally into a permanent-ON state. Investigation revealed that maintenance technicians had replaced two pneumatic manifold coils with third-party replacement valves that lacked internal surge suppression diodes. Each time a solenoid de-energized, an oscilloscope captured a −380 V inductive transient firing directly back into the 24 V DC output driver. Installing DIN-rail terminal surge modules completely eliminated further output card burnouts.

Safety & Meter Pitfall

Reversed Flyback Diode: The Dead Short Explosion

When wiring a discrete flyback diode (such as a 1N4007 or 1N5408) across a 24 V DC solenoid valve terminal block, pay meticulous attention to polarity. The cathode end of the diode (marked by a distinct white or silver painted band) MUST connect to the positive (+24 V DC) supply terminal, and the anode connects to the switched negative/transistor output line. If a diode is installed backward, it becomes forward-biased the exact instant the PLC output turns ON. This creates an immediate dead short circuit across the 24 V power supply, vaporizing the diode or destroying the PLC output channel within milliseconds.

DIAGNOSTIC SEQUENCE

Five checks before replacement

  1. Disconnect power and measure solenoid coil resistance (a standard 24 V DC 5 W pneumatic coil typically measures 110 Ω to 120 Ω).
  2. Test suppression diode with multimeter diode-test function: should read 0.5–0.7 V forward and infinite (OL) in reverse.
  3. Verify with an oscilloscope across coil terminals during de-energization: verify voltage transient does not exceed 35 V DC.
  4. Check whether the PLC output card includes built-in electronic freewheeling clamping diodes.
  5. Ensure surge suppressors are installed as close to the physical solenoid coil as possible (ideally integrated into the Hirschmann connector).
PRACTICAL NOTES

Always order solenoid valves with factory-integrated LED and varistor/diode surge suppression inside the DIN connector head.

Never install a standard DC flyback diode on an AC circuit: it will conduct during every negative half-cycle and explode.

For pneumatic valves switching more than 10 times per second, use Zener/TVS suppressors to prevent coil armature sticking.

BEFORE YOU REPLACE THE PART

Bench checklist

  • Identify the solenoid DC voltage rating: confirm 24 V DC (never install DC diodes across AC solenoid coils).
  • Verify flyback diode polarity: cathode (striped band) MUST connect to +24 V; anode connects to switched 0 V / output.
  • Measure solenoid coil resistance with power disconnected: calculate operating current (I = 24V / R_coil).
  • Verify flyback diode ratings: ensure continuous current rating (e.g. 1A for 1N4007) exceeds coil steady-state current.
  • Inspect PLC digital output module diagnostics: check for short-circuit, over-current, or thermal shutdown alarms.

Reference families

  • IEC 60947-5-1 Standard
  • Siemens SIMATIC I/O Manuals
  • Festo Pneumatic Installation Guide

Always verify the current edition and the exact device manual for the installation.

READ THE PRIMARY MATERIAL

Official references

These links point to standards bodies, industry organizations, or manufacturer documentation. Standards landing pages may require purchase or institutional access.

MV
FIELD INSTRUMENTATION & CONTROLS SPECIALIST

Marcus Vance, PE

16+ Yrs Field Exp

Marcus is a licensed Professional Engineer specializing in industrial process automation, PLC/DCS I/O commissioning, and instrumentation troubleshooting across petrochemical and manufacturing facilities.

Peer-reviewed for IEC & ISA standards compliance · Editorial methodology →
This note is an educational reference, not a substitute for the equipment manual, site procedures, or qualified electrical work.